Bob,In new HVAC condensate drain installation when the drain is run through framed walls, use of a flexible plastic drain line is common - as shown in the photo I'll attach below and as is described further at inspectapedia.com/aircond/Condensate_Drain_Problems.phpHowever in my OPINION a better installation uses rigid PVC pipe, properly sloped 1/8" to 1/4" per foot. See attached pic for mock-up. The backfill under and beside the pipe shall be compacted for pipe support. Runout piping not exceeding 4 feet (1219 mm) in length and 1 inch (25 mm) in diameter between the control valve and HVAC coil. When the AC condensate drain entry point is higher than the condensate drip pan outlet you have to either use a condensate pump - which is what I'd do - or disassemble and re-install the whole AC/Heat system to raise it so that it can drain by gravity. However a read of manufacturer's installation instructions can provide further advice. Im not sure if this is relevant to the answer, but the water heater has a neutralizer built in so that shouldnt be an issue either way. I've been having problem with my fan coil unit for a few years now. Heat Exchanger 11. Does Texas code require an attic AC drip pan to be be attached to a drain line or is it acceptable for the drain line to be capped off? broad. Theres no floor drain, but the washer standpipe is not far away. So, if we are supposed to drain the primary into the drainage system of the house, can we terminate the drain line over a gutter and let the water fall into the gutter, where it will continue to the ground to an approved area? The model same model building codes contain these very minimal requirements for traps on condensate removal lines for HVAC equipment: 1. a trap shall be installed in accordance with the unit manufacturer's installation and operating instructions, 2. the condensate drain line slope towards its final drainage point shall be at 1/8" per foot [or, of course greater, where vertical drains are used - Ed.]. MECHANICAL DESIGN CRITERIA (PROJECT STANDARDS AND SPECIFICATIONS) TABLE OF CONTENT SCOPE 2 DEFINITIONS AND TERMINOLOGY 2 UNITS 3 CODES AND STANDARDS 3 GENERAL DESIGN CRITERIA 9. Including recorded tech training, interviews, diagnostics and general conversations about the trade. Using California's Title 24 as a good example, see the table below. A neutralizer is easy to make with a length of 1 1/4 pvc pipe and some marble or lime chips. On 2021-06-03 Its also possible that this install is totally legit, and the air gap requirement is fulfilled by the gap between the ground and the down pipe outside the house. When discharging into a shared drain or sewer system, ensure that it isn't piped so that waste fumes could enter the system or occupied space. Your email address will not be published. Piping shall be at least 3/4" in diameter and shall not decrease in size [throughout its run from the condensate drain pan to its final disposal destination - no constructions by diameter]" We have no relationship with advertisers, products, or services discussed at this website. Obviously, I need to ask the builder why he didnt use the sink in the laundry room. 33822 [i.e. The vent opening should always rise above the trip level of the condensate overflow switch when it is in the primary drain line or pan or above the secondary/aux overflow port on the primary drain pan. If you're interested in reading another article about drain cleaning best practices, check out this article. P.S. Please find your question repeated along with a detailed reply now at IP Enclosures IP-GRPDD084 CONDENSATE DRAIN, distributed by Kempston Controls. Equipments 10. Thanks, Genry! RT Quick Angle Grinder - 601078420 from METABO. On 2021-02-08 Its the contractors responsibility to give them a choice and educate them about the options and what the thorough diagnostic process looks like, including balancing the home and checking the pressure in relation to the outdoors. Many will point to where the ICC energy efficiency code states: N1103.3 Mechanical system piping insulation. Plumbing Code (UPC) and the 2005 National Electrical Code." Typically a condensing tankless water heater doesnt require a condensate trap (American cited below) My company recently changed out all the hvac equipment at an apartment complex. Which allows only condensate and gases to drain from steam pipe lines a.Traps b. 3345 Sunrise Blvd.Suite 5Rancho Cordova, CA 95742, Mon Fri: 7:30 am 5:00 pmSat: 8:00 AM 2:00 PMClosed Sunday, HomeAboutServicesFinancingReviewsLearning CenterService AreasContact, Mitsubishi Variable Speed Ducted Heat Pump, get your official Fox Family merch available on Teespring.com. These pipe bevelers are used on PVC and CPVC plastic pipe including C900, Corzan CPVC, Bionax PVCO (C909) and also ABS. To get the data we need to design systems that mitigate those issues, we need to do a blower door test. An indoor disconnect switch. When its required by the manufacturers installation instructions, Sacramento area county inspectors look for a trap. Anything over 20 tons uses larger diameter piping. Notice that one of the most common condensate disposal locations, connection to a plumbing stack vent pipe, is not recommended and is prohibited by building code in some jurisdictions. Above: a pipe insulation table from the New York 2010 Energy Code. Piping that conveys fluids that have not been heated or cooled through the use of fossil fuels or electric power. Coil rust/corrosion on an HVAC evaporator caused by the unit itself and its condensation should be considered wear and - Answered by a verified HVAC Technician . Also, about that shared drain idea, Please bookmark this page to make it easy for you to check back for our response. Examples of approved areas include a trapped and ventilated receptor to a sanitary sewer, and a downspout that terminates to an approved area. not less than the drain on the unit, and in no case less than 3 4 of an inch (20 mm). I would think you need to look at the bigger picture as to where the condensate drain is connected. State Licensed Mechanical Contractor. My question is: Is it in violation of building or installation codes to not have a condensate drain line? Mechanical system piping capable of carrying fluids above 105F (40C) or below 55F (13C) shall be insulated to a minimum of R-3. blown into the unit from the outside and settle in The inspectors say we if we discharge the condensate into the houses actual drainage system, it must be by means of an indirect waste pipe. For example: "In some installations, dirt or other debris may be One thing you should prove to yourself if youre the one installing or modifying the current drain line, is to make sure you get a level on it. regular price: $408.66 (inc gst) regular price: $408.66 (inc gst) price: An old foreman of mine always liked to glue in his PVC with the lettering facing away from the perspective of the person sitting on the platform. Mechanical Engineering questions and answers. Sorry but I don't know another reliable solution. Good tips and knowledge. 4. Connection of condensate waste to sanitary plumbing and drainage systems This technical note provides clarification on the requirements for connecting condensate from refrigerated air conditioners, cabinets, sterilizers, autoclaves and similar appliances to sanitary or drainage systems. This gives your drain pipe a uniform look and makes it easy for the inspector to pass your job. health and safety concerns are reviewed. But you still need to confirm to yourself that the ENTIRE drain line has at least, an eighth-inch slope to it. Universal Single Stage Heat Pump Defrost Control, 50M56X-843 Integrated Furnace Controls Universal Replacement, Understanding Leak Detectors With Inficon, Making Cold Climate Heat Pumps Work w/ Copeland and White Rodgers, RTU Retrofits Facts and Considerations with JCI, Training for the Future w/ Clifton & ESCO, Effective Filtration & More w/ John Ellis, Do Houses Need to Breathe? Air conditioner cooling coils require a condensate drain with a trap in accordance with the manufacturer's instructions [2019 CMC 310.1]. Drains can be made out of many materials, but PVC is by far the most common. Apologies for the delay. There was considerable discussion of the condensate disposal requirements. The tables of pipe insulation shown here are interesting in that each gives insulation thickness required in inches without specifying the insulation material though Table 503.2.8 does give an assumed R-value per inch of insulation. from the 2003, 2006 and 2009 International Residential Code Air entering or leaving an HVAC unit via the condensate drain line manifests itself as an energy loss and a . CONDENSATE DRAINS, CODES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice. But that excerpt really isn't talking about condensate drains when read in context. CONDENSATE DRAIN INSULATION REQUIREMENTS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall be located at or above the elevation required by Section 1612 of the International Building Code for utilities and attendant equipment. The IMC (International Mechanical Code) is one of the most widely utilized and referenced. In the City Code, "Mechanical Code" means the 2021 Uniform Mechanical Code adopted in Section 25-12-131 (Uniform Mechanical Code) as amended by Section 25-12-133 . Whether its to support the drain line with hangars, or to strap it down to the deck, we dont want the PVC to bow downwards, creating a dip and not allowing gravity to do its thing. If youre planning to tie two evaporator drains into one single drain line, they may want you to increase the size of the final pipe going to the outside. Use threaded fittings if you want to go upscale for easier servicability. The IMC states that condensate drains should be trapped according to manufacturers' specs. While moisture in a crawl space can cause damage over time, this is not the intent of this section. 1. vibration transmission to the building framing (if the unit is installed on a wood frame floor or ceiling) will make the unit noisier than necessary2. ThIs barely leaves me 3" to work with and that is not enough for proper trap depth and insulation. Find many great new & used options and get the best deals for Evaporator Coil Condensate Drain Trap EZT-113B - BUY MORE & SAVE!!! Phoenix Mechanical Code; Sections 510(a) (Condensate Disposal) and 1701(c) (Cooling Towers; Wastewater Disposal): Sec. The requirement for the air gap on a dishwasher (you could use the same device) is to prevent accidental siphon of the trap as well as to prevent backflow of drain water into the draining appliance (dishwasher or condensate pump). Seattle has adopted the 2018 International Mechanical Code, with amendments specific to our jurisdiction. Whats pictured is a clean out with the cap missing. - use an Appliance Wye to connect a condensate drain to an existing washing machine standpipe or other drain. If the manufacturer requires a trap, then a trap is required. Residential HVAC installers have to understand so many facets of the construction industry. You'll see that in Texas there is not much chance that the condensate drain is going to be running at the operating temperature ranges ( 105F (40C) or below 55F ) cited here. Watch out: But as you'll see from the annotations on your photo there are some other questions here, including a water heater TPR valve safety concern and possible leaks into the return air duct system. Condensate or waste water shall not drain over a public way. The following are significant changes to the IMC and its proposed amendments. Condensate waste and drain line size shall not be less than 3/4-inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. It appears that this condensate drain only drops into that vertical standpipe an inch or two and if there is still a decent opening around it to let air into the standing drain line then you got an air gap between the end of the condensate drain and the P-trap below so it should be okay. * Tools to help navigate through the 2014 NYC Construction Codes 2014 Construction Codes Amendment Index So the home builder decided to install a condensation pump, but over time the pump would malfunction due to the corrosive water. Our Comment Box is provided by Countable Web Productions countable.ca, Click to Show or Hide Citations & References, Codes & recommendations for HVAC Condensate Drainage, CONDENSING BOILER/FURNACE CONDENSATE DRAIN, Al Carson, Carson Dunlop Associates, Toronto, AIR CONDITIONER SLEEVE OUTDOOR DRAIN KIT INSTALLATION INSTRUCTIONS, Amana, ARUF & ASPT AIR HANDLER INSTALLATION & OPERATING INSTRUCTIONS, Amana CONDENSING GAS FURNACE SERVICE MANUAL, AMANA GUCA GCCA CONDENSATE DRAIN LINES Ive got 20 units tied into a 2 inch pipe and recently it started getting backed up.. Provided an air vent and drain plug in the coil. Downsizing the tonnage in retrofits or replacements usually has advantages, but it must be done right, and customers may not always want to do that. The IMC code doesn't directly state that the drain line must be insulated. The material around the condensate drain and the probability that that material could, if wet, become any of the problems I've cited. This Q&A were posted originally at CONDENSATE DRAINS, CODES. I want to find a permanent solution where I can connect pvc pipe and have the water drain out to the outlet. In this case, that means read the instructions on the label of the glue being used and on the primer being used. The condensate drain from mechanical equipment is regulated by the mechanical code. Smoke pencils and other similar tools can give you an idea of the pressure in a home and how it could change when doors open or close. I have to imagine that with A/C being so much more common in the US, the only reason something similar hasn't been developed or adapted for use here is because it isn't allowed. Above: Table 503.2.8 Minimum Pipe Insulation Thickness, adapted from the 2010 New York State Energy Conservation Code. It's not directly into the sewage line but I was wondering if there's still an issue of sewage gasses backing into the home. Enforcement of the condensate-neutralization codes will likely increase as the problem . The model building codes do not explicitly require insulation on HVACR condensate drain piping, but in some circumstances that insulation might still be recommended or even required by a local code official. This mandatory cleanout allows technicians to blow-out the lines with compressed air at a later date when mold and gunk build up inside it. Water doesn't flow uphill, and if you tried raising the sides of a condensate pan to get condensate level high enough to drain by gravity alone, you're building a breeding ground for dangerous bacteria or Legionnaire's disease in the condensate that stays in the lower part of the pan. . 3. by (mod) - is condensate drain piping insulation required? origin ZIP Code, destination ZIP Code and time of acceptance and will depend on shipping service selected and receipt of cleared payment. The sink will be used daily so there's little chance for the water to evaporate and allow for sewer gases. 5.2 Roof Drainage Terminology . In SC, does the condensation line of an attic HVAC unit need to be insulated? @Hy, The only code I have found (Oregon) regarding condensate removal is in the mechanical code (which usually applies to HVAC) and this line is making me question whether the pump's output can in fact be less than 3/4": Roof Drainage Terminology. Bush down the ends, and you have a simple package. We are discussing good practice in HVACR installation: materials, routing, and possible need for insulation on the condensate drain line. I never stopped doing it that way again because it looks clean. UV resistant wrap for linesets 4. @Tom P., This allows the water to drain to the side of the house, down through the gravel and into the earth down below it and keep the sidewalk dry. by (mod) What the Mechanical Codes Say Let's take a look at what the codes say about condensate control and adherence to the code when doing an HVAC change-out. Please bookmark this page to make it easy for you to check back for our response. If you are making use of a water heater - to produce domestic hot water used for washing and bathing - water flowing through the heater is pushed by building water pressure, from a municipal supply or from a well water pump or a pressure booster pump. Uniform Mechanical Code. It coats the pan, p-trap and drain piping with a lubricative film to improve flow . Design Review.<br>3. Theres less busyness going on in the scene. Because typically the installation instructions for a condensing tankless water heater include this statement: Think of it as similar to a dishwasher installation. Piping that conveys fluids that have a design operating temperature range between 55F (13C) and 105F (41C). Puerto Rico and the U.S. Virgin Islands enforce one or more of the I-Codes. cooling coil or fuel-fired appliance that produces condensate: 1. Energy code: Section 503.2.8 Piping insulation. There are two types of drains commonly used and requested by the mechanical engineer, in addition to two functions the drains provide from a plumbing standpoint. Those are not usually very noisy; check for malfunction, for mounting on padding, for alternative models, for relocation to a more remote spot that can still pump up to the necessary drain. It should be stated and restated that codes and code enforcement vary from location to location within the US. You will not receive a notification when a response to your question has been posted. The drain drops down then runs out through the wall to the building exterior where it drains onto a roof and thence into a gutter and downspout system if not totally evaporated. Mechanical system piping capable of carrying fluids above 105F (40C) or below 55F (13C) shall be insulated to a minimum of R-3. IMO, Sure that can work, provided the tubing carrying condensate to the drain is routed such that it passes above the flood rim of the sink. Sharing a drain downstream MIGHT work depending on condensate drain material, size, capacity, routing, etc. Quoting, Also see: specific condensate drain installations for your specific air conditioner, heat pump, or condensing gas furnace. General Electric Zoneline instructions [8][9], Watch out: see the warnings and advice about health hazards in HVAC systems and condensate handling systems, This topic has moved to CONDENSATE DISPOSAL, IMPROPER. @Jack Mc., Thin aluminum rain gutters were not designed to carry this type of corrosive waste to the ground. The waste pipe shall have a slope of not less than 1/8 inch per foot (10.5 mm/m) or one percent slope and shall be of approved corrosion-resistant material not smaller than the outlet size as required in either Section 310.3 or 310.4 below for air-cooling coils or condensing fuel-burning appliances, respectively. In this blog, well be talking about the importance of installing condensate drain lines correctly so the system doesnt cause damage to your customers home. Coil shall be tested at 500 psi (35 kg/sq.) Bob, continuingHere is Diversitech's 5/8" flexible AC condensate drain tubing - sold at Home Depot and at HVACR suppliers and plumbing suppliers, What type of piping or tubing is used for condensation drainage inside a wall on an inside unit of a split unit. Thats why we call it a gravity drain because as long as we have the necessary 1/8 inch of downward slope for every 12 inches of carry, gravity will do all the work and pull the condensate waste to the ground all by itself. Please take a look. 5. The most recent code is the International Mechanical Code (IMC). Check it periodically and clean, if necessary." Steam line b. But a trap at the heater is probably required. Available in over 20 convenient sizes. Updated 3/4/2022 Picking up where we left off in part 2 of the series, we discussed how a pressure reading from an attached zone indicates only the ratio of the [], 2023 - HVAC School | All rights reserved. This creates a nuisance area of slippery water that, over time, can even start creating algae which are even more slippery. But I hope this answers some questions you have about the building code, HVAC installations, and condensate drain lines. Thanks, Michael! And check out many related blog posts here. If youve ever wanted Fox Family swag, heres your chance to grab the same stuff we wear on the job out in the field! Youve installed the new system and now that youve adapted into the existing drain line, you own the whole drain line. This is in a ground level garage. Demonstrated abilities in cementing healthy relationship with clients and leading workforce towards accomplishing business and corporate goals.<br>4. Does anyone have any information about this topic? Make sure to check the installation manual if you have two systems. For the secondary drain system he installed a wet switch within the pan below the unit which will turn the unit off upon water detection. appliance, device or apparatus, may discharge into, the drainage system" 3. Materials 10. While venting is a common best practice, it isn't part of the IMC code. On 2020-01-16 by (mod) - placing an air handler on top of mason bricks sitting inside the drip tray proper installation procedure? (CMC 312.1) 2. Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. AND DRAIN TRAP INSTRUCTIONS, Intertek CVC96 7 MVC96 TWO STAGE GAS FURNACE INSTALLATION INSTRUCTIONS, RECTORSEAL EZ TRAP CONDENSATE DRAIN LINE INSTRUCTIONS, RHEEM NON-CONDENSING TANKLESS WATER HEATER INSTALLATION MANUAL, AMERICAN COMMERCIAL CONDENSING TANKLESS WATER HEATER INSTALLATION MANUAL, ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS, HOME INSPECTION EDUCATION COURSES (Canada), HOME INSPECTION EDUCATION: HOME STUDY COURSES, 307.2: " Condensate shall not "The information in this guide is a summary of requirements ASHRAE Standard 90.1-2010, Section 6.4.4.1 HVAC System Pipe Insulation, lists HVAC piping requirements and as an EXCEPTION, The condensate line material: Sch. Code (IPC), International Mechanical Code (IMC), 2006 Uniform Thanks for your help On 2022-01-17 by Inspectapedia Com Moderator - follow glue and primer manufacturer instructions. Chapter 7 of the International Plumbing Code relative to the material type. Thank you for your help with this matter. Carson Dunlop Associates sketches (left) illustrate both acceptable and not-recommended locations for the discharge of an air conditioner or heat pump condensate drain line discharge. A little further up the drain, toward the evaporator coil, the question is, do we have to install a p-trap or not? They both say pretty much the same thing. My OPINION is that the pump itself - the container and motor, sold as a unit - is separable from the drain piping or tubing. Recently learned for 5 ton draw-through systems, the 3/4 PVC exiting the coil needs several inches of vertical drop to sufficiently create enough water volume & weight to stop back pressure which clearly created spillage/leakage from the drain pan. On 2020-09-09 by (mod) - primary condensate drain had been capped off with no outlet. They simply state that drain systems must be trapped, leaving design to others. What are the specs of pipe needed to drain 20 units that are all over 3 tons each? Both require an air gap - which you have, and neither should be overwhelming a properly-sized, un-blocked drain. IMC 307.2.3 states that all HVAC equipment that produces condensate must have either a secondary drain line or a condensate overflow switch, a secondary drain pan with a secondary drain line, a condensate switch, or some combination of these installations should be used to prevent overflow if the primary drain line blocks. A condensing gas-fueled tankless water heater would be expected to operate at a greater overall fuel efficiency than a comparable non-condensing unit. That would include the main plumbing vent stack. [BS]301.16 Flood hazard. Working on a school and they love high ceilings. @InspectApedia , thank you the advice. what is the code for the primer used for gluing pvc schdule 40 pipe for refrigeration evaporators in a 36 degree cooler? Factory-installed piping within HVAC equipment tested and rated in accordance with a test procedure referenced by this code. I was afraid that would be the recommendation. Include piping material and sizes on the mechanical plans. do not discharge HVACR condensate over a sidewalk. Table 307.2.2 states: "3/4 up to 20 tons" Is this the same code you are referencing? Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly. Lets take a look at what the codes say about condensate control and adherence to the code when doing an HVAC change-out. They both say pretty much the same thing. We also provide an ARTICLE INDEX for this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need. Some condensate products might be too hot for the piping used for an HVAC condensate drain - such as that thinwall flexible plastic tubing found at many installations, (condensate from a condensing tankless water heater is at about 38C or about 100F) but standard PVC pipe, if that's what was used for the drain, should be OK. Factory-installed piping within room fan-coils and unit ventilators tested and rated according to AHRI 440 (except that the sampling and variation provisions of Section 6.5 shall not apply) and 840, respectively. The most recent code is the International Mechanical Code (IMC). Are these considered the same item or are the pump and lines two different items? Thank you! 17,112 satisfied customers. Some building design features also exacerbate problems presented by oversized HVAC systems. A condensing gas-fueled tankless water heater recaptures much of the heat that would have gone up the flue, uses it to help heat the domestic hot water, and produces a much-cooler exhaust and condensate that is typically vented through PVC piping to the exterior. DavidThe overflow drip pan can be capped off provided that there is a water sensor switch installed that will shut down the AC system if the pan receives condensate water. [9] "GE Zoneline Owners Manual and Installation Instructions, Heat Pump Model 5800", General Electric Corporation, [copy on file]. According to the IMC, 3/4 is sufficient for up to 20 tons unless the drain outlet size is larger than 3/4. The black tubing in the photo is actually foam insulated refrigerant piping. We have all kinds of great videos about your homes hvac system. If that's the case the owner ought to have had that information before the sale was completed. Are there currently any plumbing codes that prevent A/C condensate from being used for toilet flushing? [10] "Whirlpool WGPH45 Packaged Heat Pump, Product Specifications", Whirlpool Corporation, [copy on file]. Is this okay? IT couldn't handle the volume, nor the flow rate, nor the duty cycle. Certainly there is no conceptual constraint on where a condensate drain can be located, but it has to be in a location that works either by gravity or by a condensate drain pump. Where pipe insulation is required the requirement depends on pipe size, use, and temperatures that will be encountered. Does this sound right? My company recently changed out all the hvac equipment at an apartment complex. Your condensate line, also known as a "condensate drain line" or "condensate drain" does several jobs, but none are more critical to the functionality of your appliance than draining excess moisture outside of your home. In practice, it is safer to use 1/4 of fall per foot to ensure proper drainage and provide some wiggle room for error. (p. 3) It is the final part of his series on zonal pressure diagnostics. There's a p-trap. stock code: afs-le85-2. I'm preparing to install a DIY mini split on the back wall of my garage which is an interior wall. Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. overflow of the primary drain pan or blockage of the condensate drain piping. Does anyone have any information about this topic? -- [Thanks to Al Carson, Carson Dunlop Associates, Toronto], Note: new in 2015 is the ICC IMC 307.2.5 & IRC M1411.3.3 Drain Line Maintenance code for 2015, The ICC, under "Drain Line Maintenance" requires that, Condensate drains shall be configured to permit the clearing of blockages and performance of maintenance without having to cut the line.